CMC-MX series built-in bypass type motor soft starter
-
Category:Variable frequency energy-saving transmission
- Click count:
- Release date:2024/07/09
- Online inquiry
Introduction to CMC-MX built-in bypass soft starter:
CMC-MX built-in bypass motor soft starter is a voltage regulating and current limiting intelligent asynchronous motor soft starter based on trigger closed-loop algorithm. Its superior power electronic circuit detection and advanced closed-loop control algorithm make the starting and protection functions more perfect. The built-in bypass contactor contact adopts a magnetic retention type contactor, which is different from other external bypass AC contactors that operate with electricity for a long time. This product is noise free, electromagnetic pollution-free, spark free, and environmentally friendly.
CMC-MX built-in bypass soft starter function:
It can start/stop the motor smoothly without any step, avoiding mechanical and electrical impacts caused by traditional starting methods such as direct starting, star/delta starting, and self coupling voltage reduction starting. It can also effectively reduce the starting current and distribution capacity, avoiding investment in capacity expansion. At the same time, the CMC-MX soft starter integrates current transformers and contactors internally, so users do not need to connect them externally.
CMC-MX built-in bypass soft starter model description:
CMC-MX built-in bypass soft starter features:
1. Multiple starting methods
Users can choose between current limiting start and voltage ramp start, and can apply programmable jump start and starting current limit in each mode. Satisfy on-site requirements and achieve good start-up results.
2. Reliability
The microprocessor digitizes the signals in the control system, avoiding excessive adjustments to analog circuits in the past, thus achieving good accuracy and execution speed.
3. Powerful anti-interference capability
All external control signals are optoelectronic isolated and have different levels of noise resistance, suitable for use in special industrial environments.
4. Easy adjustment method
The control system has a wide range of applications, simple and intuitive adjustment methods, and can match various different control objects through various functional options.
5. Optimized structure
The unique compact internal structure design is particularly convenient for users to integrate into existing systems, saving them the cost of current transformers and bypass contactors.
6. Power frequency adaptation
Power frequency 50/60Hz adaptive function, convenient for users to use.
7. Analog output
4-20mA current output function, convenient for users to use.
8. MODBUS-RTU communication
During network communication, 32 devices can be connected. Users can achieve automatic communication by setting the baud rate and communication address. The communication address setting range is 1-32, and the factory value is 1. The communication baud rate setting range is: 0, 2400; 1. 4800; 2. 9600; 3. 19200; The factory value is 2 (9600).
9. Complete protection functions
Multiple motor protection functions (such as overcurrent, input/output phase loss, thyristor short circuit, overheat protection, leakage detection, electronic thermal overload, internal contactor failure, phase current imbalance, etc.) ensure that the motor and soft starter are not damaged in the event of faults or misoperation.
10. Easy to maintain
A monitoring signal coding system composed of 4-digit digital displays, which monitors the working status of system equipment 24 hours a day and provides fast fault diagnosis.
CMC-MX built-in bypass soft starter usage conditions:
Control power supply | AC110V--220V±15%,50/60Hz |
Three-phase power supply | Standard wiring AC380V Internal triangular wiring AC380V ± 30% |
Nominal current | 15A-560A, with a total of 18 rated values |
Applicable motor | General squirrel cage AC asynchronous motor |
Starting ramp mode | Current limiting soft start and voltage ramp start |
Parking methods | Free parking and soft parking |
Logic input | Impedance 1.8K Ω, power supply+15V |
Start frequency | Can be started frequently or infrequently, it is recommended to start no more than 10 times per hour |
Protection function | Phase failure, overcurrent, short circuit, SCR protection, overheating, under load, phase current imbalance, wiring, internal faults, etc |
Protection level | IP00、IP20 |
Cooling method | Natural cooling or forced air cooling |
Installation method | Wall mounted |
Environment condition | If the sea level exceeds 2000 meters, the capacity should be correspondingly reduced for use The ambient temperature is between -25-+45 ° C The corresponding humidity shall not exceed 95% (20 ° C ± 5 ° C) No flammable, explosive, corrosive gases, no conductive dust, indoor installation, good ventilation, vibration less than 0.5G |
Basic wiring diagram of CMC-MX built-in bypass soft starter:
The terminals 1L1, 3L2, and 5L3 of the soft starter are connected to the three-phase power supply, and 2T1, 4T2, and 6T3 are connected to the motor. No external bypass contactor is required, and the soft starter can select whether to detect phase sequence through parameter settings.
Triangle Inner Connection Diagram
If the user uses a triangular internal connection, they must strictly follow the following diagram for connection, otherwise it may cause damage to the motor or soft starter. Before starting the machine, the motor wiring will be checked. If there is a wiring error, the soft start will report a wiring error fault.
Appendix 1: Selection of Standard Wiring Specifications and Accessories for Soft Start (Taking 380V as an Example):
Adapted motor (KW) | Soft starter model | Rated current (A) | Primary line specifications (Copper wire) |
7.5 | CMC-MX008/3 | 18 | 6 mm2 |
11 | CMC-MX011/3 | 24 | 10 mm2 |
15 | CMC-MX015/3 | 30 | 16 mm2 |
18.5 | CMC-MX018/3 | 39 | 16 mm2 |
22 | CMC-MX022/3 | 45 | 16 mm2 |
30 | CMC-MX030/3 | 60 | 25 mm2 |
37 | CMC-MX037/3 | 76 | 25 mm2 |
45 | CMC-MX045/3 | 90 | 35 mm2 |
55 | CMC-MX055/3 | 110 | 50 mm2 |
75 | CMC-MX075/3 | 150 | 70 mm2 |
90 | CMC-MX090/3 | 180 | 20×3Copper bar |
110 | CMC-MX110/3 | 218 | 20×3Copper bar |
132 | CMC-MX132/3 | 260 | 25×3Copper bar |
160 | CMC-MX160/3 | 320 | 30×3Copper bar |
185 | CMC-MX185/3 | 370 | 30×4Copper bar |
220 | CMC-MX220/3 | 440 | 40×5Copper bar |
250 | CMC-MX250/3 | 500 | 40×5Copper bar |
Note: Standard wiring refers to the delta or star connection of the motor winding, with the thyristor connected between the power supply and the motor.
Appendix: Specification and Model Selection of Soft Start Internal Triangle Wiring and Accessories (Taking 380V as an Example)
Adapted motor (KW) | Soft starter model | Rated current (A) | Primary line specifications (铜线) |
7.5 | CMC-MX008/3 | 18 | 6 mm2 |
11 | |||
15 | CMC-MX011/3 | 24 | 10 mm2 |
18.5 | |||
22 | CMC-MX015/3 | 30 | 16 mm2 |
30 | CMC-MX022/3 | 45 | 16 mm2 |
37 | CMC-MX030/3 | 60 | 25 mm2 |
45 | |||
55 | CMC-MX037/3 | 76 | 25 mm2 |
75 | CMC-MX055/3 | 110 | 50 mm2 |
90 | CMC-MX075/3 | 150 | 70 mm2 |
110 | |||
132 | CMC-MX090/3 | 180 | 20×3Copper bar |
160 | CMC-MX110/3 | 218 | 20×3Copper bar |
185 | CMC-MX132/3 | 260 | 25×3Copper bar |
220 | CMC-MX160/3 | 440 | 30×3Copper bar |
250 | CMC-MX185/3 | 500 | 30×4Copper bar |
280 | CMC-MX220/3 | 630 | 40×5Copper bar |
315 |
Note: Internal delta connection refers to the series connection between the motor winding delta thyristor and the winding. The main advantage of inner triangle control is that soft starters can be selected for derating. In the inner triangle connection method, the current flowing through the soft starter and motor is 1/√ 3 of the line current. The above table uses a margin selection soft starter, selected according to the line current/1.5 times the rated current. During the selection process, users can further reduce the rating and select a soft starter according to the actual situation.
Ordering Notice
When placing an order, users should inform the supplier of the product model, specifications, load conditions, and usage conditions in order to select the product correctly.
The standard configuration of the soft starter includes a built-in current transformer and a built-in contactor, and users do not need external current transformers and bypass contactors.
The attachments in the above table are for reference only.
Appendix 2: Appearance and Opening Dimensions of Soft Starters (Unit: mm, Taking 380V as an Example):
CMC-MX series built-in bypass soft starter selection:
Number | Rated current(A) | 380V | Size(mm) |
Adaptive power(KW) | 173×275×192 (width x height x thickness) | ||
1 | 18 | 7.5 | |
2 | 24 | 11 | |
3 | 30 | 15 | |
4 | 39 | 18.5 | |
5 | 45 | 22 | |
6 | 60 | 30 | |
7 | 76 | 37 | |
8 | 90 | 45 | |
9 | 110 | 55 | |
10 | 150 | 75 | 285×450×305 (width x height x thickness) |
11 | 180 | 90 | |
12 | 218 | 110 | |
13 | 260 | 132 | |
14 | 320 | 160 | |
15 | 370 | 185 | |
16 | 440 | 220 | 320×523×305 (width x height x thickness) |
17 | 500 | 250 |
For more information on the installation direction, installation space, circuit installation, circuit connection, terminal instructions, display and operation instructions, control mode, parameter items and instructions, fault detection and troubleshooting, communication control, daily maintenance, and selection of soft starters for CMC-MX built-in bypass soft starters, you can click directly